Difference between revisions of "Cable Routes and Protection"

From DIYWiki
Jump to navigation Jump to search
Line 18: Line 18:
 
OR
 
OR
  
e) be installed in a [[Safe_zones_for_electric_cables|safe zone]] and have 30mA RCD protection.
+
e) be installed in a [[Safe_zones_for_electric_cables|safe zone]] . The 17th edition also requires cables in the safe zone to be protected with a 30mA RCD.
  
 
Note 1 - If the wall or partition is made from or partially made from metal than the cable will require RCD protection
 
Note 1 - If the wall or partition is made from or partially made from metal than the cable will require RCD protection

Revision as of 11:01, 24 October 2010

This page is Under Construction
Whilst all Wiki pages are subject to continuing improvement the author(s) of this page have included this disclaimer to alert the reader that the page may be particularly
  • incomplete - important sections may be entirely missing
  • inaccurate - significant facts and figures may be quite wrong
  • misleading - the text may not convey the author(s) intended meanings

In particular treat any safety-related sections of the text (e.g. relating to electrical work) with great caution.

If you are thinking of editing this page please be aware that the original author(s) of this page may be actively working on it at this moment, so changes you make may clash with theirs. (The Wiki software will warn you of conflicts if this happens.) Checking the page's history tab for frequent recent edits can warn you if changes by others are likely.


Some basic rules for the installation of cables to protect them from damage

Cables in a wall or partition

A cable concealed in a wall or partition must

a) be at least 50mm from the surface [note 1]

b) have earthed armouring or an earthed metal sheath (eg SWA, a BS 8436 cable or MICC cable)

c) be enclosed in earthed steel conduit or trunking

d) be provided with mechanical protection (3mm steel is deemed sufficient to meet this requirement)

OR

e) be installed in a safe zone . The 17th edition also requires cables in the safe zone to be protected with a 30mA RCD.

Note 1 - If the wall or partition is made from or partially made from metal than the cable will require RCD protection

Cables Underground

External Cables