Difference between revisions of "Lighting Circuits Without an Earth"

From DIYWiki
Jump to navigation Jump to search
(asstd small)
Line 1: Line 1:
 
==Background==
 
==Background==
Many lighting circuits (usually installed pre 1966) are still in use that have no earth (aka Circuit Protective Conductor (CPC)).
+
Many [[House Wiring for Beginners|lighting circuits]] (usually installed pre 1966) are still in use that have no earth (aka Circuit Protective Conductor (CPC)).  
 
Whilst the rewiring of these circuits is the preferable solution, for many people the cost of installation and redecorating can be prohibitive.
 
Whilst the rewiring of these circuits is the preferable solution, for many people the cost of installation and redecorating can be prohibitive.
  
  
 
==Safety==
 
==Safety==
Metal light fittings or switches on an unearthed circuit are a shock risk. If insulation fails, and that's not a rarity, the fitting will often become live. Touching that is a risk to life. One cause of insulation failure is buildup of dirt at connection points, something that happens over the years.
+
Metal light fittings or switches on an unearthed circuit are a shock risk. If insulation fails, and that's not a rarity, the fitting will often become live. Touching that is a risk to life. One cause of insulation failure is buildup of [[:Category:Cleaning|dirt]] at connection points, something that happens over the years.
  
Since unearthed lighting circuits are generally around half a century old, they tend to lack other safety features expected in a modern installation, some of which are very basic and necessary. These include:
+
Since unearthed lighting circuits are generally around half a century old, they fall short on other safety features expected in a modern installation, some of which are very basic and necessary. Common problems include:
  
1. Badly perished rubber insulation.
+
1. Badly perished [[Historic Mains Cables|rubber insulation]].
  
2. Light switches that can sit in mid position, and if luck deserts you, sit in an almost on position and arc. This either burns the switch out or causes a fire.
+
2. Light switches that can sit in mid position, and if luck deserts you, sit in an almost on position and arc. This either burns the switch out or causes a [[fire]].
  
3. Non-EEBAD installation. Such installations can fail to blow a fuse when necessary, occasionally resulting in risk to life.
+
3. Non-EEBAD installation. Such installations can fail to blow a [[fuse]] when necessary, occasionally resulting in risk to life.
  
 
4. Dirt buildup at connection points. This can cause insulation breakdown, a fire & shock risk.
 
4. Dirt buildup at connection points. This can cause insulation breakdown, a fire & shock risk.
Line 22: Line 22:
  
 
7. Light switch covers that undo easily by hand, a danger primarily to children.
 
7. Light switch covers that undo easily by hand, a danger primarily to children.
 +
  
 
==Reducing risk==
 
==Reducing risk==
If a rewire is not an option then the following steps should be taken for safety reasons
+
If a rewire is not an option then the following steps should be taken for safety reasons:
  
 
:# Metal (Class I insulated) light fittings and metal accessories should be replaced with (Class II) fittings, which are either plastic, or metal and marked with the [[]] Class II symbol.
 
:# Metal (Class I insulated) light fittings and metal accessories should be replaced with (Class II) fittings, which are either plastic, or metal and marked with the [[]] Class II symbol.
:# Insulation Resistance Test. The circuit should be tested between the line conductor (line and neutral connected together) and the earth terminal of the consumer unit. The resistance should be at least 1 Megohm. If the resistance is less that 1 Megohm the circuit must have additional [[RCD]] protection. The test should also be repeated between the line conductor and any exposed conductive part of the circuit (eg the [[screws]] for a lightswitch with a metal backbox). Again if the readings are less than 1 Megohm then additional [[RCD]] protection will be required.
+
:# Insulation Resistance Test. The circuit should be tested between the line conductor (line and neutral connected together) and the earth terminal of the [[CU|consumer unit]]. The resistance should be at least 1 Megohm. If the resistance is less that 1 Megohm the circuit must have additional [[RCD]] protection. The test should also be repeated between the live & neutral conductors and any exposed conductive part of the circuit (eg the [[screws]] for a lightswitch with a metal backbox). Again if the readings are less than 1 Megohm then additional [[RCD]] protection is necessary.
:# RCD protection. It is advisable to have 30mA RCD protection on lighting circuits that have no cpc and essential if the resistance readings are lower than 1 Megohm.
+
:# RCD protection. It is advisable to have 30mA [[RCD]] protection on lighting circuits that have no cpc, and essential if the resistance readings are lower than 1 Megohm.
 
:# 2 and 3 pin sockets. Any 2 or 3 pin sockets connected to the lighting circuit that may be used for portable equipment should be disconnected.
 
:# 2 and 3 pin sockets. Any 2 or 3 pin sockets connected to the lighting circuit that may be used for portable equipment should be disconnected.
 
:# A warning notice similar to the one below should be fixed on or adjacent to the [[CU]] or fusebox:
 
:# A warning notice similar to the one below should be fixed on or adjacent to the [[CU]] or fusebox:
 
[[Image:Warning-notice-lights.png|center|400px]]
 
[[Image:Warning-notice-lights.png|center|400px]]
 +
  
 
==Potential problems==
 
==Potential problems==
Line 44: Line 46:
  
 
===Unsuitable wire===
 
===Unsuitable wire===
Most 2 core circuits are wired with [[Historic Mains Cables|historic flex]] that can handle the current of the lighting circuit. But there are also circuits wired up using entierly unsuitable wire in use, such as [[Low voltage wiring|bell wire]] and [[Low voltage wiring|speaker wire]]. These are a significant fire risk, and indicate seriously substandard work. If such wire is found it really needs rewiring.
+
Most 2 core circuits are wired with [[Historic Mains Cables|historic flex]] that can handle the current of the lighting circuit. But there are also circuits wired up using entirely unsuitable wire in use, such as [[Low voltage wiring|bell wire]] and [[Low voltage wiring|speaker wire]]. These are a significant fire risk, and indicate seriously substandard work. If such wire is found it really needs rewiring.
 +
 
 +
Some people refuse to rewire in such situations. In this cas at least switching from [[filament lamp]]s to [[CFL]] can at least reduce the risk considerably, due to their much lower power consumption.
  
Some people refuse to rewire such things, in which case switching from [[filament lamp]]s to [[CFL]] can at least reduce the risk considerably.
 
  
 
== See Also ==
 
== See Also ==
 +
* [[House Wiring for Beginners]]
 
* [[Earthing Types]]
 
* [[Earthing Types]]
 
* [[TT Earthing]]
 
* [[TT Earthing]]

Revision as of 23:37, 26 February 2011

Background

Many lighting circuits (usually installed pre 1966) are still in use that have no earth (aka Circuit Protective Conductor (CPC)). Whilst the rewiring of these circuits is the preferable solution, for many people the cost of installation and redecorating can be prohibitive.


Safety

Metal light fittings or switches on an unearthed circuit are a shock risk. If insulation fails, and that's not a rarity, the fitting will often become live. Touching that is a risk to life. One cause of insulation failure is buildup of dirt at connection points, something that happens over the years.

Since unearthed lighting circuits are generally around half a century old, they fall short on other safety features expected in a modern installation, some of which are very basic and necessary. Common problems include:

1. Badly perished rubber insulation.

2. Light switches that can sit in mid position, and if luck deserts you, sit in an almost on position and arc. This either burns the switch out or causes a fire.

3. Non-EEBAD installation. Such installations can fail to blow a fuse when necessary, occasionally resulting in risk to life.

4. Dirt buildup at connection points. This can cause insulation breakdown, a fire & shock risk.

5. Poor connections. Connections can deteriorate due to decades of thermal cycling, wire corrosion, or less than ideal design & construction of historic fittings.

6. Flammable wiring enclosures, such as wooden pattresses behind light switches.

7. Light switch covers that undo easily by hand, a danger primarily to children.


Reducing risk

If a rewire is not an option then the following steps should be taken for safety reasons:

  1. Metal (Class I insulated) light fittings and metal accessories should be replaced with (Class II) fittings, which are either plastic, or metal and marked with the [[]] Class II symbol.
  2. Insulation Resistance Test. The circuit should be tested between the line conductor (line and neutral connected together) and the earth terminal of the consumer unit. The resistance should be at least 1 Megohm. If the resistance is less that 1 Megohm the circuit must have additional RCD protection. The test should also be repeated between the live & neutral conductors and any exposed conductive part of the circuit (eg the screws for a lightswitch with a metal backbox). Again if the readings are less than 1 Megohm then additional RCD protection is necessary.
  3. RCD protection. It is advisable to have 30mA RCD protection on lighting circuits that have no cpc, and essential if the resistance readings are lower than 1 Megohm.
  4. 2 and 3 pin sockets. Any 2 or 3 pin sockets connected to the lighting circuit that may be used for portable equipment should be disconnected.
  5. A warning notice similar to the one below should be fixed on or adjacent to the CU or fusebox:
Warning-notice-lights.png


Potential problems

Extending the circuit

Not having an earth wire on a lighting circuit makes it impossible to extend the circuit for extra lighting points in a way that meets current wiring regulations. Extension can in principle be done safely if all switches, pattresses and lights are insulated, but regulations have demanded an earthed lighting circuit since 1966.

One viable workaround to add lighting points, is to feed them via another circuit that does have an earth wire. This can be another more recent lighting circuit, or can be a socket circuit via an fused connection unit (with appropriate fuse).

Consumer unit upgrades

Many electricians may also refuse to swap a fusebox for a CU unless the old lighting circuit is also rewired.

Unsuitable wire

Most 2 core circuits are wired with historic flex that can handle the current of the lighting circuit. But there are also circuits wired up using entirely unsuitable wire in use, such as bell wire and speaker wire. These are a significant fire risk, and indicate seriously substandard work. If such wire is found it really needs rewiring.

Some people refuse to rewire in such situations. In this cas at least switching from filament lamps to CFL can at least reduce the risk considerably, due to their much lower power consumption.


See Also