Buried column
 
'buried' column
Line 17: Line 17:


--[[User:John Rumm|John Rumm]] 03:33, 17 May 2007 (BST)
--[[User:John Rumm|John Rumm]] 03:33, 17 May 2007 (BST)
Could do. Or you could add a column or more, might be more informative. Upto you.
[[User:NT|NT]] 08:25, 17 May 2007 (BST)

Revision as of 07:25, 17 May 2007

Buried column

I was not sure what the intention of the "buried" column was going to be. Since BS7671 has a number of versions of buried that could be used:

Method 2 : Buried direct in building materials - this is treated as method 1 (clipped direct)

Method 6 : In conduit in thermally insulating wall with one side in contact with a thermally conductive surface

Method 7 : cables in conduit in masonry

and then there is cable in insulating material which seems to have no "method", but counts for a 50% de-rating straight off.

Methods 1 and 2 are the most likely to be met during DIY I would guess, followed by 7

Any thoughts? Or scrap the column and point em at BS7671 or the OSG?


--John Rumm 03:33, 17 May 2007 (BST)


Could do. Or you could add a column or more, might be more informative. Upto you. NT 08:25, 17 May 2007 (BST)