Difference between revisions of "Diversity"

From DIYWiki
Jump to navigation Jump to search
 
Line 7: Line 7:
  
 
==Allowances for Diversity==
 
==Allowances for Diversity==
 
'''Table 4B1'''
 
  
 
{| border="1" cellpadding="6" cellspacing="0" style="text-align:center"
 
{| border="1" cellpadding="6" cellspacing="0" style="text-align:center"
Line 16: Line 14:
 
! Notes
 
! Notes
 
|-
 
|-
| Lighting || 66% of total current
+
| Lighting || 66% of total current ||
 
|-
 
|-
 
| Heating and Power || 100% of total demand up to 10A, + 50% of the remainder. || Where space heating is connected to a general purpose power circuit.
 
| Heating and Power || 100% of total demand up to 10A, + 50% of the remainder. || Where space heating is connected to a general purpose power circuit.
Line 22: Line 20:
 
| Cooking appliances || 100% of total demand up to 10A, + 30% of the remainder. || Add a further 5A if a socket is fitted to the cooker point.
 
| Cooking appliances || 100% of total demand up to 10A, + 30% of the remainder. || Add a further 5A if a socket is fitted to the cooker point.
 
|-         
 
|-         
| Water heaters (instant) || 100% of first appliance, 100% of second, and 25% of any remaining appliances.
+
| Water heaters (instant) || 100% of first appliance, 100% of second, and 25% of any remaining appliances. ||
 
|-
 
|-
| Water heaters (storage) || No diversity allowable
+
| Water heaters (storage) || No diversity allowable ||
 
|-
 
|-
| Under floor heating || No diversity allowable
+
| Under floor heating || No diversity allowable ||
 
|-         
 
|-         
| Storage Heaters || No diversity allowable
+
| Storage Heaters || No diversity allowable ||
 
|-
 
|-
| Standard Circuits  || 100% of current demand of largest circuit. + 40% of demand for every other circuit.
+
| Standard Circuits  || 100% of current demand of largest circuit. + 40% of demand for every other circuit. || These are standard final circuits as described in appendix 8 of the OSG
 
|}
 
|}
  

Revision as of 21:31, 28 January 2011

(work in progress)


Diversity in this context is all about how one establishes the maximum demand for an electrical installation or an electrical circuit. The guidelines shown here are some of those as presented in the On Site Guide. Note however that these are just that - guidelines. They are based on statistical probabilities and typical usage. As a circuit or installation designer you may choose to make less flexible assessments of current demand based on your knowledge of the actual installation.

Note also that the figures presented here are for domestic properties only.

Allowances for Diversity

Purpose of circuit Diversity applicable (domestic) Notes
Lighting 66% of total current
Heating and Power 100% of total demand up to 10A, + 50% of the remainder. Where space heating is connected to a general purpose power circuit.
Cooking appliances 100% of total demand up to 10A, + 30% of the remainder. Add a further 5A if a socket is fitted to the cooker point.
Water heaters (instant) 100% of first appliance, 100% of second, and 25% of any remaining appliances.
Water heaters (storage) No diversity allowable
Under floor heating No diversity allowable
Storage Heaters No diversity allowable
Standard Circuits 100% of current demand of largest circuit. + 40% of demand for every other circuit. These are standard final circuits as described in appendix 8 of the OSG

Allowances at point of use

See Also